ups

Skirtumai

Čia matote skirtumus tarp pasirinktos versijos ir esamo dokumento.

Link to this comparison view

Next revision
Previous revision
Last revision Both sides next revision
ups [2015/04/13 13:59]
dalius sukurtas
ups [2015/04/20 12:53]
dalius
Linija 7: Linija 7:
 upsc apc@localhost\\ upsc apc@localhost\\
  
 +''​UPS Model         ​4 ​ 5  6  0    Hex   ​Firmware\\
 +SU250               EE F8 B1\\
 +SU400               EE F8 9F    E1\\
 +SU600               EA F4 9F    E5\\
 +SU900               F3 FC 9F    ED\\
 +SU1250 ​             EE FA 9F    F5\\
 +SU2000 ​             F1 F9 9F    FD\\
 +SU450,​700 ​       28 F2 FA 96 07,​RM=47 ​ 52.11.I\\
 +SU450XL,​700XL ​   28 EE F8 9F 700XL=27 ​  ​51.9.I\\
 +SU1000,​INET ​     35 EF F9 A0    0B     ​60.11.I\\
 +SU1000XL ​        34 EE FC 9A    2B      61.9.I\\
 +SU1400 ​          35 EE FC 9A           ​70.11.I\\
 +SU1400RM ​        28 ED FA 89\\
 +SU1400R2IBX135 ​  08 B4 10 A3\\
 +SU1400RMXLI3U ​   45 F6 F4 80            73.x.I\\
 +SU1400RMXLI3U ​   20 F3 FD 81            73.x.I\\
 +SU2200I ​         35 EE FB AF           ​90.14.I\\
 +SU2200XL,​3000 ​   35 EE FB AF 3000=17 ​  ​90.14.I\\
 +SU3000RMXLI3Ublk 35 F3 F4 AF    77     ​93.14.I\\
 +SU5000I white    20 F2 FA 91    1F    110.14.I\\
 +SU1400XL,​XLI,​RM ​ 45 F6 E4 80\\
 +SU420I ​          25 95 09 85    16      21.7.I\\
 +SU420SI ​         0E 95 0A 8C\\
 +SU620I ​          29 99 0B 8A    1A\\
 +BP420SI ​         0E 95 0A 8C    06      11.2.I\\
 +BP650SI ​         10 97 0C 91    0A      12.3.I\\
 +Power Stack 250  0C 95 0F B2            26.5.I\\
 +Power Stack 450  0D 96 10 99    36      26.5.I\\
 +SC250RMI1U ​      0C 95 0F B3    32     ​735.a.1\\
 +SC420I ​          0E 95 OA 8C    16     ​725.1.I\\
 +SC620I ​          10 97 OB 99    1A     ​726.x.I\\
 +SC1000I ​         08 95 10 94    8A     ​737.x.I\\
 +SC1500I ​         07 95 14 8F    1E     ​738.x.I\\
 +SU1000XL ​        17 EE F9 D5\\
 +MATRIX 3000,​5000 ​   E9 F5 B0\\
 +SU700RMI2U ​      07 B1 0D 92    8A     ​152.4.I\\
 +SU1000RMI2U ​     08 B5 0D C7    8E     ​157.3.I\\
 +SU1400RMI2U ​     08 B4 10 A3    92     ​162.3.I\\
 +SUA1000I ​        07 B5 13 BC    0A    652.12.I\\
 +SUA1000XLI ​      0B BD 0F 7F    4A    681.13.I\\
 +SUA750XLI ​       0A B9 0C 86    46     ​630.3.I\\
 +SUA750I ​         04 B6 14 82    06    651.12.I\\
 +SUA750RMI2U ​     07 B1 0D 82    86    619.12.I\\
 +SUA1500I ​        09 B9 13 A1    0E 601/​653.x.I\\
 +SUA1500RMI2U ​    08 B4 10 A1    8E     ​617.3.I\\
 +SUA2200I ​        08 B8 12 B3    26    654.12.I\\
 +SUA2200RMI2U ​    09 BC 11 81    A6     ​665.4.I\\
 +SUA2200XLI ​      0A B7 0F 7F    66     ​690.x.I\\
 +SUA3000RMI2U ​    04 B9 0E 70    AA     ​666.4.I\\
 +SUA3000RMXLI3U ​  0A B6 0E 89    xx     ​xxx.x.x\\
 +SUOL1000I ​       06 B6 1B A6\\
 +SUOL2000XL ​      0D BD 14 75    52     ​416.5.I\\
 +SURT1000XLI ​     0A BB 19 A8    4E     ​411.x.I\\
 +SURT3000XLI ​     06 B6 0F CC    56     ​450.2.I\\
 +SURT5000XLI ​     05 BA 15 86    5A    451.13.W\\
 +SURT7500XLI ​     03 BB 20 97    63\\
 +SURT10000XLI ​    06 B8 19 AB          476.12.W\\
 +SUM1500RMXLI2U ​  03 B7 0D A5    62     ​716.3.I\\
 +SUM3000RMXLI2U ​  03 B7 0D A5    6A     ​715.3.I\\
 +BP500AVR ​                       26      17.1.I\\''​\\
 +
 +Select the serial port to which black serial cable is connected to.  The correct settings for the COM-connection are 2400 Baud, 8 data bits, 1 Stop bit, no parity, protocol Xon/Xoff. In this window, click on Advanced and make sure that the option FIFO activated is unchecked. Click twice on OK.\\
 +
 +Check if there is a connection (Type Shift + Y, should return **SM** ). Do not enter any other characters via Hyperterminal other than that described in these instructions because this can cause irreparable damage to the UPS\\
 +
 +Type **1**, wait 2-3 secs and type **1** again (Should return **Prog**)\\
 +
 +Enter a **0** and the UPS reports the present value of the battery constant. ​ If this value does not correspond to the default value that was given to you by RM Support or APC , it must be changed.\\
 +
 +If this value is not correct, press **+** or **-** until the correct value is returned.\\
 +
 +Press **R** to close the session. (Should return **Bye**)\\
 +
 +Enter **<​Shift>​ Y**, the UPS reports again with **SM**.\\
 +
 +Enter **0** once again and check if the UPS reports back the standard setting that has been set.\\